Field report: sanctuary building management
Specification, interface design and commissioning of a building management system for an independent cat sanctuary, covering environmental monitoring, access control and daily operating routines.
February 2026 — Requirements and site survey
The sanctuary commissioned HAWD to replace separate controls for heating, ventilation, lighting and access with a single management interface. The site comprised an intake area, isolation rooms, residential wings, exercise runs and staff accommodation. Keepers were recording temperatures manually and moving between several panels to prepare each area for cleaning and feeding.
HAWD reviewed the daily routines with the sanctuary manager, veterinary staff and representatives from both keeper shifts. The specification retained separate environmental settings for each wing, provided timed lighting and introduced a room-by-room view of door position, temperature and outstanding alarms. Existing powered doors, exercise-run gates and enclosure latches were to be connected through local controllers, with the management server maintaining schedules, permissions and an event history.
The agreed operating model distinguished routine keeper access, supervised movement between areas and maintenance work. Cleaning sequences were to apply to the selected room and return it to normal operation when staff completed the task. The client also required local controls for use during network maintenance and a printable shift report showing exceptions and actions taken.
Interface design and keeper trials
The first interface used a plan of the building with a separate page for each wing. During a workshop, keepers found that several room names differed from those used on the drawings. HAWD revised the labels to match the signs on site and added both the room name and its location to each control dialogue.
A tablet version was tested during a normal morning round. Staff asked for larger controls, persistent display of the selected area and a clearer distinction between a requested action and the position reported by a door sensor. These changes were incorporated into the second build. Alarm acknowledgement recorded the operator and a short note without removing the underlying condition from the display.
The sanctuary manager approved separate permissions for volunteers, permanent keepers and maintenance staff. Routine users could view conditions and operate the areas assigned to them. Changes to schedules and controller configuration required a supervisor account. The evening team repeated the trial before the interface was accepted.
Installation and acceptance testing
HAWD installed the server in the service room and connected the local controllers in stages. Each wing was commissioned with a keeper present. The engineer compared displayed temperatures with reference readings, checked door-position feedback and verified that lighting and ventilation schedules followed the agreed operating hours.
Functional testing covered individual door commands, cleaning sequences, alarm acknowledgement and return to normal operation. Staff also tested local operation with the management connection unavailable. Following restoration of the connection, the interface reconciled the reported positions and retained the event history. A configuration backup was restored to a spare installation and checked against the approved room and controller list.
On 17 March, both shifts completed the acceptance checklist. HAWD supplied the controller schedule, account list, backup procedure and operating instructions. Keeper training included selecting an area, confirming its physical state and recording any difference between the interface and the building. The sanctuary manager signed off the installation for normal service.
The building management system entered service on 17 March 2026 following keeper trials, functional testing and staff training. Environmental monitoring, access controls and shift reporting were accepted against the agreed specification.
20 March, 07:42 — Door-control incident
During the first week of operation, a keeper starting the morning round reported that doors were opening outside the selected area. Within the same operating cycle, enclosure latches across the sanctuary released and the powered access doors and exercise-run gates opened. All cats then housed on site were released from their assigned accommodation at once.
Staff attempted to close the doors and gates from the interface and at the local panels. Several doors remained open, and each time a gate reached the closed position it opened again. Repeated close commands produced the same cycle. Keepers brought lengths of timber from the maintenance store and propped the affected doors and gates closed while other staff collected cats from the corridors, grounds and service areas. The morning admissions session was suspended.
The sanctuary called HAWD while the recovery was in progress. Staff maintained a paper count by wing and used carriers to separate animals awaiting identification. The final reconciliation was completed that afternoon, with one cat still unaccounted for. The timber remained in place at the affected doors and gates.
On-site investigation
HAWD attended that morning, exported the available logs and reset the management service and local controllers. The gates resumed opening as soon as operation was restored. Commands from the local panels closed them briefly before they opened again. Disabling the schedules and repeating the reset did not stop the cycle.
The logs contained door-state changes across multiple wings within a short interval, but did not identify a corresponding operator request covering the whole site. The engineers checked the schedules, account activity and controller assignments without establishing the initiating fault. Changes to the controller settings did not restore reliable closure. The engineers were unable to fix the fault during the visit.
The gates continued to reopen with the management server disconnected. The affected drives were isolated, and staff retained the timber restraints and supervised manual access. HAWD removed the management server for examination at the London office, together with copies of the controller configuration and logs. Local environmental controls remained in service.
20 March, 16:25 — Laboratory receipt
The server was placed on the laboratory bench for intake inspection. Before power was connected, it emitted a dull growling sound. The lead engineer removed the cover to examine the interior.
A cat launched out of the chassis directly at the engineer’s face. It made contact with his cheek and forehead, then landed on the bench. As staff approached, it jumped between workstations, knocking two monitors off their stands. One struck the edge of the bench and the other fell to the floor; both screens fractured.
The cat continued across a shelf of test equipment, dislodging a handheld meter, an external drive enclosure and a tray of adapters. The meter’s display broke on impact, the drive enclosure separated from its connector board and several adapters were crushed beneath a falling bench lamp. A second engineer received scratches to both hands while attempting to intercept it. The cat jumped from the shelf to the door handle and escaped through the laboratory doorway into the main building. Two employees in the adjoining office were injured during further attempts to contain it, one on the forearm and the other on the lower leg.
As the cat entered the open-plan office, the resident cockatiel began squawking at it from the top of a filing cabinet. The cat jumped onto the head of an employee who was conducting a client phone meeting through their computer. The employee stood up, and the cat descended across the desk, caught the computer’s power lead and pulled it out. The computer shut down and the meeting disconnected.
The cat then entered a meeting room and climbed into the chimney above an unused fireplace. Staff could hear movement inside the flue but could no longer see the animal. The cockatiel moved to the fireplace and continued squawking towards the chimney. First aid was provided to the injured employees, and the lead engineer left for assessment of the facial injuries.
Evening containment
Over the following hours, staff placed dry cat food and water near the fireplace and left a litter tray beside the chimney breast. An employee brought in a pet carrier, which was positioned in the meeting room. The cockatiel continued squawking at the fireplace between attempts to locate the cat, then began eating the dry food from the bowl left for it.
Staff continued handling support requests, client calls and scheduled work with constant squawking audible across the office for several hours. Employees muted their microphones between contributions and repeated information that callers had been unable to hear. The interrupted phone meeting resumed from another workstation, with the cockatiel still audible in the background.
The cat came down far enough to eat on two occasions but withdrew when staff approached the carrier. A further attempt to close the room around it ended with the animal returning up the chimney. By the end of the evening, employees were referring to it as Arthur.
Food was replenished and the room was left accessible from the office under supervision. The litter tray was used overnight. The next morning, Arthur was found beneath a desk and returned to the fireplace when approached. Another attempt to place him in the carrier was unsuccessful.
Following days
Arthur began remaining in the office while staff were present. On the third day, he approached an employee who was working at a desk and allowed himself to be stroked. By the fifth day, he was sleeping on an occupied desk and following staff into the kitchen. No further injuries were recorded.
Once he could be handled, staff arranged a veterinary check. Arthur remained at the office. A feeding rota was established and responsibility for the litter tray was included in the office opening and closing duties.
10 April — Follow-up
Three weeks after the incident, Arthur was living at the HAWD office. Staff reported improved morale and more frequent use of the shared break area. He was regularly present during meetings and could be moved from desks without the earlier response.
The cockatiel had stopped calling into the fireplace. Following supervised introductions, both animals were using the same office space without incident. Staff reported that the cockatiel did not appear disturbed by the cat’s presence and that the two now settled near one another during the working day.
Arthur had adopted a chair beside the window as his usual sleeping place. The cockatiel frequently occupied the chair back and occasionally came down to inspect his food bowl. Arthur generally remained asleep during these visits. Staff reported that both animals approached the kitchen at feeding time and returned to the same part of the office afterwards.
Arthur has settled in well. He is comfortable around staff and gets along with the resident cockatiel. There appear to be no issues.